Availability: | |
---|---|
Technical specifications
Type | VCH5102 | VCH5106 |
Frame current (A) | 25 | 63 |
Standards | IEC 61095 | IEC 60947-4-1 |
Number of poles | 2, 4 | |
Type of current | AC | |
Frequency (Hz) | 50/60 | |
Rated voltage Un (V) | 230/400 | |
Rated current In in AC-7a / AC1 (A) | 10, 16, 20, 25 | 25, 32, 40, 63 |
Rated current In in AC-7b / AC1 (A) | 4, 5.5, 7, 8.5 | 8.5, 12, 15, 25 |
Rated power in AC3 (Kw) | ||
230 V | 2-5 | 5-13 |
400 V | 6-13 | 15-40 |
Control circuit voltage (V) | 24, 230 | |
Mechanical life (times) | 2.5 | |
Electrical life (times) | ||
AC-7a / AC1 | 10,000 | 80,000 |
AC-7b / AC1 | 50,000 | 40,000 |
Degree of protection | IP20, with connected conductors | |
Conductor cross-sections | ||
Solid and stranded (mm²) | 2-25 | |
Finely stranded with end sleeve (mm²) | 2-25 | |
Terminals | ||
Terminal tightening torque (N·m) | 0.8-2.4 | |
Ambient temperature (°C) | -5 ~ +40, max. 95 % humidity | |
Storage temperature (°C) | -40 ~ +75 | |
Connection capacity (mm²) | 1-25 |